Hoe moeten ABB-energiemeters worden beveiligd tegen overbelasting en kortsluiting?

  1. Voor directe meters geldt:

    Type: A41 en A43: met een installatieautomaat van maximaal 80 A (B- of C-karakteristiek) of zekering van maximaal 80 A (gL-gG-type).

    Type: B21 en B23: met een installatieautomaat van maximaal 65 A (B- of C-karakteristiek) of zekering van maximaal 65 A (gL-gG-type).

    Type: C11 en C13: met een installatie-automaat van maximaal 40 A (B- of C-karakteristiek) of zekering van maximaal 40 A (gL-gG-type).

    Voor indirecte meters geldt:

    Type: A42, A44, B24:

    Voor de spanningsmeting: met een installatie-automaat maximaal 10 A, B-karakteristiek of 10 A type gL-gG.

    Voor de stroommeting: in de secundaire kring van stroomtransformatoren mag nooit een beveiliging voorzien worden.

Heeft dit antwoord u geholpen?

Ja Nee

Terug naar Energiemeters overzicht

Bent u op zoek naar ondersteuning of aankoopinformatie?

Neem contact met ons op

Contactinformatie

Mocht u een vraag hebben die niet in de lijst voorkomt? Stel hem dan gewoon aan een van onze medewerkers via nl-tech-EP@abb.com onder vermelding van 'FAQ'.

Meer informatie nodig?

ABB Technical Support

ABB Technical Support

Naam ABB Technical Support
Telefoon 088 2600 900